Fire Pull Station Height
Another important aspect associated with device placement involves the height at which it must be mounted.
Fire pull station height. Ada fire extinguisher heights and fire alarm pull station placement must allow wheelchair users access and ease of operation. Through a forward reach or a side reach. In a forward reach the wheelchair user approaches the object head on. Not less than 2300 mm above the floor where ceiling heights allow measured to the centre of the device.
1200 1400 mm above the floor measured to the centre of the manual station the centre of the back box 1050 1150 mm above the floor measured to the centre of the manual station the centre of the back box audible signalling appliance. Sections 22 3 4 2 and 23 3 4 2 of nfpa 101 require fire alarms to initiate manually as well as by any detection devices that may be required in other parts of the code. But just like pulling the fire alarm may be done to get kids out of class a pull station might look like a get out of jail free card to an inmate. 2 in a building that is sprinklered a manual pull station is not required at an exterior egress.
Manual fire alarm boxes pull stations the height of the manual fire alarm boxes shall be a minimum of 42 inches and a maximum of 54 inches measured vertically from the floor level to the activating handle or lever of the box. The ontario building code manual pull stations 3 2 4 18. Nfpa 72 the national fire alarm and signalling code requires the operating switch of manual pull stations to be located between 42 and 48 inches from the floor. Below we have an picture of a typical manual pull station.
The ada provides two ways to make operable parts accessible to wheelchair users. Manual pull stations 1 except as permitted by sentences 2 and 3 if a fire alarm system is installed a manual pull station shall be installed a near the principal entrance to thebuilding and b near every required exit. In this case height is measured from the floor to the operable part of each manual fire alarm box according to section 5 13 4 of nfpa 72 2007 edition mounting height must be between 3 and 4 feet from floor to handle.